  • Measuring principle

    Application manager

  • Measuring principle

    Batch controller

  • Function

    Filling & dosing

  • Calculations

    Volume calculation

  • Number of applications

    1

  • Data storage

    yes

  • Calculation standards

    ASTM D1250-04

  • Communication

    RS232
    USB
    Ethernet
    Modbus TCP
    Modbus RTU

  • Power supply

    Not defined

  • Loop power supply

    Low voltage power supply:
    100 bis 230 V AC (-15% / +10%)
    Small voltage power supply:
    24 V DC (-50% / +75%)
    24 V AC (±50%)

  • Protection class

    IP65

  • Input

    1 x analogue (I) / pulse (for flow)
    1 x RTD (for temperature)
    1 x analogue (I) (for density)
    Loop power supply 24V DC (+/-16%)

  • Output

    1 x analogue (I) / pulse (active)
    2 x open collector

  • Dimensions (WxHxD)

    144 x 144 x 103.1 mm (5.67" x 5.67" x 4.06")

  • Operation

    3 operation buttons and 14 function buttons for batch operation or via FieldCare
    Read out of historical / logged data via Field Data Manager software (SQL database and visualization interface)
    Selectable language

  • Display

    160 x 80 Dot-Matrix LCD with white backlit
    Colour change in case of alarm event
    Active display area 70 x 34 mm

  • Software functions

    Volume calculation
    1 or 2 stage operation
    Manual and automatic overrun correction
    Volume correction factor (VCF) according ASTM D1250-04 for generalized crude oils, refined products and lubricating oils

  • Certificates

    CE
    CSA GP
    NTEP (USA)

  • Measuring principle

    Batch controller

  • Function

    Filling & dosing

  • Certification

    CE
    UL listed
    CSA GP

  • Input

    1 x analogue (I) / pulse (for flow)
    1 x RTD (for temperature)
    1 x analogue (I) (for density)
    Loop power supply 24V DC (+/-16%)

  • Output

    1 x analogue (I) / pulse (active)
    2 x open collector

  • Relay output

    2 x relay

  • Auxiliary power supply / Loop power supply

    Low voltage power supply:
    100 bis 230 V AC (-15% / +10%)
    Small voltage power supply:
    24 V DC (-50% / +75%), 24 V AC (±50%)

  • Dimensions (wxhxd)

    144 x 144 x 103.1 mm
    (5.67" x 5.67" x 4.06")

  • Software

    Volume calculation
    1 or 2 stage operation
    Manual and automatic overrun correction
    Volume correction factor (VCF) according ASTM D1250-04 for generalized crude oils, refined products and lubricating oils

  • Operation

    3 operation buttons and 14 function buttons for batch operation or via FieldCare
    Read out of historical / logged data via Field Data Manager software (SQL database and visualization interface)
    Selectable language

  • Display

    160 x 80 Dot-Matrix LCD with white backlit
    Colour change in case of alarm event
    Active display area 70 x 34 mm